Technical Data
Temperature – NTC
-
Measuring range -4° to 158 °F / -20 to +70 °C
-
Accuracy ±1 °F (32° to 158 °F) / ±0.5 °C (0 to +70 °C) , ±1.4 °F (-4° to 32 °F) / ±0.8 °C (-20 to +0 °C)
-
Resolution 0.1 °F / 0.1 °C
-
Reaction time 45 sec (t90)
Humidity – Capacitive
-
Measuring range 0 to 100 %rH
-
Accuracy ±1.8 %rH + 3 % of mv at +77 °F / ±1.8 %RH + 3 % of mv at +25 °C (5 to 80 %rH)
-
Resolution 0.1 %rH
Differential Pressure
-
Measuring range -0.480 to 0.480 InH₂O / -120 to +120 Pa
-
Accuracy ±2 % of mv + 0.002 InH₂O at +72 °F, 405 InH₂O / ±2 % of mv + 0.5 Pa at +22 °C, 1013 hPa
-
Resolution 0.001 InH₂O / 0.001 Pa
-
Reaction time 1 sec (t90)
Absolute Pressure
-
Measuring range 280 to 440 InH₂O / 700 to 1100 hPa
-
Accuracy ±1 InH₂O / ±3 hPa
-
Resolution 0.1 InH₂O / 0.1 hPa
-
Reaction time 1 sec
Volume Flow
-
Measuring range 24 to 2354 CFM / 40 to 4000 m³/h
-
Accuracy ±3 % of mv + 7 CFM at +72 °F / ±3 % of mv + 12 m³/h at +22 °C 405 InH₂O (50 to 2060 CFM) / 1013 hPa (85 to 3500 m³/h)
-
Reaction time 1 sec (t90)
-
Resolution 1 CFM / 1 m³/h
General Technical Data
-
EU-/EG-guidelines EU-guideline 2014/30/EU
-
Battery type Alkaline, type AA
-
Battery life 40 h
-
Display size 3.5"
-
Display function Dot matrix
-
Display ligthing with illumination
-
Interface Micro-USB; Bluetooth® 4.0 wireless technology
-
Memory 2 GB (internal)
-
Storage temperature -4° to 140 °F / -20 to +60 °C
-
Weight 102 oz. / 2900 g
-
Dimensions 24 x 24 in. (Standard hood) / 610 x 610 mm (Standard hood)
-
Operating temperature 23° to 122 °F / -5 to +50 °C